This regulator is among domestic models for industrial and commercial applications. Compared to GS-74-27 , it enjoys higher incoming pressure range and outflow capacity.
Features:
- The operation is unilateral and It never starts up with exerting pressure into the outlet.
- In case of the flow changes at the inlet, the outflow remains constant.
- If the outgoing flow is stopped ( Q=0 ) with maximum incoming pressure , the regulator goes on normal operation and the blocked pressure would not exceed the specified limit.
- The regulator can be installed under different positions wih the possibility to rotate the diaphragm casing in an angel of 360 to the body.
Safety equipment installed on Gas Souzan’s GS-74-27H regulators is:
According to the NIGC’s orders and in order to increase safety level for consumers , three safety systems are considered in this regulator.
- Shutting off gas flow in case of the outlet pressure drop-lower than the specified limit (LPSO).
- Shutting off gas flow in case of the outlet pressure ise beyond the specified limit (HPSO)
- Automatic relief valve for case of gas flow overpressure.
Technical Data
| 1 – 9 bar (15 – 130 psig) |
Inlet Pressure |
15 – 600 mbar (¼ -8.5psig)
|
Out Pressure |
| (40 ) m3/h |
Capacity |
| 2" NPT |
Inlet |
Connection |
2" NPT
|
Out let |
| 1" NPT |
Vent |
| Low Pressure Safety Shut Off Valve |
Equipped with |
| High Pressure Safety Shut Off Valve |
| Safety Relief Valve |
| (-20 to +60) C |
Operating Temperature |
330 x 578 x 324mm
|
Dimantion |
|
Material
|
Description
|
|
Cast
IRON A126 CLASS B
|
Body
|
|
Die Cast
Aluminum ASTM B85
|
Diaphragm
housing
|
|
Reinforced
Rubber; NBR
|
Diaphragm
|
|
NBR;
|
Seat
|
|
SINTERING
POWDER ;steel; specialalloy
|
Toggle
|
Safety Syste
|
Low pressure shut off
|
High pressure shut off
|
Relief valve
|
| Pout(mbar) |
| 20 |
8.5±1.2
|
42.3±2.5 |
62.35±7.5 |
| 30 |
10±1.2 |
45±2.5 |
65±7.5 |
| 40 |
13.7±1.2 |
47.5±2.5 |
67.5±7.5 |
| 70 |
26.6<41.3 |
109.3<122.6 |
153.2<189.2 |
| 138 |
54.9<82.6 |
219.9<259.9 |
309.2<379.9 |
Safety system set point
Typical regulation curve
Overal Dimension
Max capacity (M³/h) with orifice size 8.5(mm)
138
|
70
|
40 |
30 |
20 |
Pout(mbar)/Pin(bar) |
| 80 |
70
|
65 |
40 |
66 |
0.5 |
| 100 |
80
|
80 |
55 |
84 |
1 |
| 120 |
110
|
115 |
70 |
115 |
1.5 |
| 145 |
125
|
135 |
95 |
130 |
2 |
| 165 |
150
|
155 |
120 |
150 |
2.5 |
| 185 |
170
|
175 |
135 |
160 |
3 |
| 205 |
195
|
195 |
145 |
165 |
3.5 |
| 230 |
215
|
210 |
150 |
175 |
4 |
| 255 |
230
|
230 |
160 |
190 |
4.5 |
| 280 |
260
|
235 |
165 |
200 |
5 |
| 285 |
270
|
240 |
180 |
210 |
5.5 |
| 290 |
275
|
240
|
200 |
210 |
6 |
| 308 |
290
|
260 |
215 |
220 |
6.5 |
| 330 |
315
|
280
|
230 |
240 |
7 |
| 350 |
335
|
300
|
250 |
260 |
7.5 |
| 380 |
360
|
32
|
265 |
280 |
8 |
| 400 |
380
|
340 |
280 |
290 |
8.5 |
| 425 |
405
|
360
|
300 |
310 |
9 |
ing Dimansion in diferent Pressure330
| 138 |
70 |
40 |
30 |
20 |
Pout(mbar) |
| Dimansion(mm) |
| 179±3 |
179±3 |
168± 2 |
168±2 |
185± 3 |
A |
| 56.5± 0.2 |
54.5± 0.2 |
51.5± 0.2 |
51.5± 0.2 |
50.8± 0.2 |
B |
| 6± 0.0 |
4.5± 0.0 |
4± 0.0 |
4± 0.0 |
3.5± 0.0 |
C |
| 10 CCW |
10 CCW |
10 CCW |
10 CCW |
12 CCW
|
D |